Why Correct Sizing Matters
An undersized generator will overload, overheat and fail prematurely. An oversized generator runs inefficiently, wastes fuel and increases maintenance costs. Correct sizing ensures reliability and lowest total cost of ownership.
Step 1: List All Loads
Make a list of all equipment that must run during a power outage. Record each item's running power (kW) and starting power (kW or kVA).
Step 2: Apply Diversity Factor
Not all loads run at the same time. Multiply the total running load by a diversity factor, typically 0.6 to 0.8 for commercial buildings and 0.8 to 1.0 for critical facilities like hospitals.
Step 3: Account for Motor Starting Current
Electric motors draw 5-7 times their running current during startup. Use soft starters, VFDs or oversized generators to handle these inrush currents without voltage dip.
Step 4: Convert kW to kVA
Generator capacity is usually rated in kVA. Use the formula: kVA = kW / Power Factor. Typical power factor is 0.8. For example, a 400kW load requires at least 500kVA generator capacity.
Step 5: Add Future Expansion
Add 20-30% spare capacity for future load growth. This also improves fuel efficiency and extends engine life.
Quick Reference Table
| Application | Typical Range |
|---|---|
| Small office/shop | 20kVA - 60kVA |
| Commercial building | 100kVA - 500kVA |
| Factory | 500kVA - 2000kVA |
| Data center | 1000kVA+ with N+1 redundancy |